(可調流量平衡閥)自力式控制閥
簡要描述:RETZ (可調流量平衡閥)進口自力式控制閥用于需要進行流量控制的水系統中,尤其適用于供熱、空調等非腐蝕性液體介質的流量控制。運行前一次性調節,即可使系統流量自動恒定在要求的設定值
品牌:RETZ
工況條件:調節
溫度/壓力:P-T:16bar-120℃
更新時間:2022/08/17
技術參數 Technical paramete
(可調流量平衡閥)進口自力式控制閥由自動調節閥瓣和手動調節閥瓣兩部分組成。當系統流體工作壓差超過300KPa時,為防止產生噪音,應采取措施將多余的壓差消耗掉 RETZ self operated adjustable flow control valve (balance valve) is composed of two parts: automatic regulating valve disc and manual regulating valve disc. When the working pressure difference of system fluid exceeds 300kPa, measures shall be taken to consume the excess pressure difference to prevent noise
平衡閥不具備關斷功能,根據需要應另設關斷閥門。系統流體的工作壓力為P1,手動調節閥瓣的前后壓力分別為P2、P3。當手動調節閥瓣調到某一位置時,即人為確定了“設定流量”,以及相對應的固定(P2 -P3)值。當系統流量增大時,(P2-P3)的實際值超過了允許的給定值,此時自動調節閥瓣自動關小,直至流量重新維持到設定流量,反之亦然 RETZ balance valve does not have the shut-off function, and another shut-off valve shall be set as required. The working pressure of the system fluid is P1, and the front and rear pressures of the manual regulating valve disc are P2 and P3 respectively. When the manual regulating valve flap is adjusted to a certain position, the "set flow" and the corresponding fixed (P2 - P3) value are determined manually. When the system flow increases, the actual value of (P2-P3) exceeds the allowable given value, at this time, the automatic regulating valve disc automatically closes until the flow is maintained to the set flow again, and vice versa
尺寸:F2"-20" Size: F2 "- 20"
工作溫度:0~90℃ Working temperature: 0 ~ 90 ℃
承壓等級:PN16 Pressure bearing grade: PN16
控制精度∶ ±8% Control accuracy: ± 8%
壓差范圍∶20-300KPa Pressure difference range: 20-300kpa
工作介質∶冷、熱水 Working medium: cold and hot water
連接方式∶法蘭 Connection method: flange
閥體材質∶球墨鑄鐵 Valve body material: ductile iron
密封材質∶EPDM Sealing material: EPDM
(可調流量平衡閥)進口自力式控制閥 性能特點∶ Performance characteristics
1、能使系統流量自動平衡在要求的設定值 The system flow can be automatically balanced at the required set value
2、能自動消除水系統中因各種因素引起的水力失調現象,保持用戶所需流量,克服“冷熱不均”,提高供熱,空調的室溫合格率 retz can automatically eliminate the hydraulic imbalance caused by various factors in the water system, maintain the flow required by users, overcome the "uneven cold and heat", and improve the room temperature qualification rate of heating and air conditioning
3、能有效地克服“大流量,小溫度”的不良運行方式,提高系統能效 It can effectively overcome the bad operation mode of "large flow and small temperature" and improve the energy efficiency of the system